1592010880 XWEB3000_5000 EVO OPR GB r1.0 2014.11.28 59/100
Class Name: class name used in the configuration of the dew-point engine.
Typology Filter: filter allowing for the display of only the chosen device list.
For each device represented in the list, it is defined:
- Check enabled: defines whether or not the device is part of the class
- Set Dew Variable: defines the variable towards which the dew-point value will be sent. Attention: if the
Set Dew Point variable is not visible in the list, it has probably been disabled by the tool advances.
Access Device-SetupAdvances and enabling.
- Offset: value added to the Set Dew value. Reflects the difference between the temperature read by the
XM600 probe that is not normally fitted on the glass and the real glass temperature.
To modify an existing class, access the menu “ClassEdit Class”
To eliminate an existing class, access the menu “ClassRemove Class”.
With keys:
- Select/Deselect All: select/deselect all devices in the list, combining them with the class
- Create: to confirm the parameters entered in the window and create the class
- Cancel: to close the window without confirming the entered parameters
Dew-point Engine Configuration
Access the menu OperationEngine Parameters X representing the Dew-point management engine number
to be run
Each of these engines can be configured with the following parameters: